Delta Electronics AC Motor Drive VFD-G User Manual
Page 81

Chapter 4 Parameters|
4-30
Revision July 2008, EG03, SW V1.06
01 - 19
JOG Frequency
Unit: 0.1sec
Settings
0.0
Hz~160.00
Hz
Factory Setting: 6.00
When the JOG function is to be utilized, users need to use the multi-function input terminals
(Pr. 04-00 to 04-03 set to 07) or the JOG key on keypad. Once a JOG command is initiated,
the AC drive will accelerate from the Minimum Output Frequency (Pr.01-05) to the JOG
frequency (Pr.01-19).
The accel/decel time of the JOG operation is determined by the JOG accel/decel speed
(Pr.01-17 and 01-18).
When the drive is in operation, the JOG command is disabled.
01 - 20
S Curve Delay Time in Accel
01 - 21
S Curve Delay Time in Decel
Settings
0.00~2.50sec
Factory Setting: 0.00
These parameters enable the S curve. The longer the S curve time period the smoother the
transition between speeds.
01 - 22
Modulation Index
Unit: 0.1
Settings
0.90~1.20
Factory Setting: 1.00
This parameter sets the ratio of the Maximum Output Voltage to the input voltage.
The Maximum Output Voltage (Pr.01-02) is normally limited to the input voltage. With the
Modulation Index parameter, the user is able to increase the output voltage beyond the
incoming line voltage.
A Modulation Index of 1, defines the Maximum Output Voltage (Pr. 1-02) is equal to the input
voltage.
A Modulation index of 1.2, defines the Maximum Output Voltage (Pr. 1-02) is 20% higher than
in the input voltage. Please note, the output voltage wave form will be distorted due to
harmonics and may increase torque ripple and noise in the motor.
01 - 23
Accel/Decel Time Unit
Factory Setting: 01
Settings
00: Unit is 1 Sec
01: Unit is 0.1 Sec
02: Unit is 0.01 Sec
This parameter sets the resolution of accel/decel time (Pr.01-09 to 01-18).