Chapter 4 Parameters|

4-30

Revision July 2008, EG03, SW V1.06

01 - 19

JOG Frequency

Unit: 0.1sec

Settings

0.0

Hz~160.00

Hz

Factory Setting: 6.00

When the JOG function is to be utilized, users need to use the multi-function input terminals

(Pr. 04-00 to 04-03 set to 07) or the JOG key on keypad. Once a JOG command is initiated,

the AC drive will accelerate from the Minimum Output Frequency (Pr.01-05) to the JOG

frequency (Pr.01-19).

The accel/decel time of the JOG operation is determined by the JOG accel/decel speed

(Pr.01-17 and 01-18).

When the drive is in operation, the JOG command is disabled.

01 - 20

S Curve Delay Time in Accel

01 - 21

S Curve Delay Time in Decel

Settings

0.00~2.50sec

Factory Setting: 0.00

These parameters enable the S curve. The longer the S curve time period the smoother the

transition between speeds.

01 - 22

Modulation Index

Unit: 0.1

Settings

0.90~1.20

Factory Setting: 1.00

This parameter sets the ratio of the Maximum Output Voltage to the input voltage.

The Maximum Output Voltage (Pr.01-02) is normally limited to the input voltage. With the

Modulation Index parameter, the user is able to increase the output voltage beyond the

incoming line voltage.

A Modulation Index of 1, defines the Maximum Output Voltage (Pr. 1-02) is equal to the input

voltage.

A Modulation index of 1.2, defines the Maximum Output Voltage (Pr. 1-02) is 20% higher than

in the input voltage. Please note, the output voltage wave form will be distorted due to

harmonics and may increase torque ripple and noise in the motor.

01 - 23

Accel/Decel Time Unit

Factory Setting: 01

Settings

00: Unit is 1 Sec
01: Unit is 0.1 Sec
02: Unit is 0.01 Sec

This parameter sets the resolution of accel/decel time (Pr.01-09 to 01-18).