Chapter 2 Installation and Wiring|

Revision July 2008, EG03, SW V1.06

2-11

2.4 Control Terminals

Terminal

Symbol

Terminal Function

Factory Settings

FWD Forward-Stop

command

FWD-DCM:
ON: Run in FWD direction
OFF: Ramp to stop

REV Reverse-Stop

command

REV-DCM:
ON: Run in REV direction
OFF: Ramp to stop

EF External

fault

EF-DCM:
ON: External Fault. Display “EF” and coast/ramp to stop
OFF: No fault

MI1 Multi-function

Input

1

MI2 Multi-function

Input

2

MI3 Multi-function

Input

3

MI4 Multi-function

Input

4

MI1~MI4-DCM:
Refer to Pr.04-00~Pr.04-03 for programming multi-
function inputs.
ON: the activation current is 16mA.
OFF: leakage current tolerance is 10μA.

+24V

DC Voltage Source

+24V 20mA
used for Source mode.

DCM Digital

Signal

Common

Used as common for digital inputs and used for Sink
mode.

AFM1

Analog output meter 1

0 to 10V, 2mA
Impedance: 470Ω
Output current: 2mA max
Resolution: 8 bits
Range: 0 ~ 10VDC
Function: Pr.03-05

AFM2

Analog output meter 2

Load Impedance: ≦500Ω
Output current: 20mA max
Resolution: 8 bits
Range: 0/4 ~ 20mA
Function: Pr.03-06

AOM

Analog control signal common Used as common for analog outputs.

RA1

Multi-function Relay1 output
(N.O.) a

RB1

Multi-function Relay1 output
(N.C.) b

RC1

Multi-function Relay1
common

Resistive Load:
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Inductive Load:
1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
Refer to Pr.03-00 for programming.