Delta Electronics AC Motor Drive VFD-G User Manual

Page 5

background image

WARNING!

1.

DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor

drive is easily damaged by high-pressure.

2.

There are highly sensitive MOS components on the printed circuit boards. These components

are especially sensitive to static electricity. To prevent damage to these components, do not

touch these components or the circuit boards with metal objects or your bare hands.

3.

Only qualified persons are allowed to install, wire and maintain AC motor drives.

CAUTION!

1.

Some parameter settings will cause the motor to run immediately after applying power.

2.

DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight,

high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic

particles.

3.

Only use AC motor drives within specification. Failure to comply may result in fire, explosion or

electric shock.

4.

To prevent personal injury, please keep children and unqualified people away from the

equipment.

5.

When the motor cable between the AC motor drive and motor is too long, the layer insulation of

the motor may be damaged. Please use a frequency inverter duty motor or add an AC output

reactor to prevent damage to the motor. Refer to appendix B Reactor for details.

6.

The rated voltage for the AC motor drive must be

≤ 480V for 460V models and the mains

supply current capacity must be

≤ 5000A RMS (≤10000A RMS for the ≥ 40hp (30kW) models).