beautypg.com

Group 8 special parameters – Delta Electronics AC Motor Drive VFD-G User Manual

Page 65

background image

Chapter 4 Parameters|

4-14

Revision July 2008, EG03, SW V1.06

Parameter

Functions

Settings

Factory

Setting

Customer

07-08 Calculate

Total

Running Time of the
Motor (Min)

00 to 1439 Min

00

07-09 Calculate

Total

Running Time of the
Motor (Day)

00 to 65535 Day

00

07-10

Electric Bill for One
Time

Read Only

Read

07-11 Accumulated

Electric

Bill (per currency unit)

Read Only

Read

07-12 Accumulated

Electric

Bill (per 10

4

currency

unit)

Read Only

Read

07-13

Electric Rate (per
currency unit)

0.01 to 655.35

0.6

Group 8 Special Parameters

Parameter

Functions

Settings

Factory

Setting

Customer

08-00

DC Braking Current
Level

00~100% 00

08-01

DC Braking Time
during Start-up

0.0~60.0 Sec

0.0

08-02

DC Braking Time
during Stopping

0.00~60.00 Hz

0.0

08-03 Start-point

for

DC

Braking

0.00~160.00 Hz

0.00

08-04 Momentary

Power

Loss Operation
Selection

00: Disable
01: Trace from top downward
02: Trace from bottom upward

00

08-05 Maximum

Allowable

Power Loss Time

0.1~5.0 Sec

2.0

08-06

Speed Search Time

0.1~5.0 Sec

0.5

08-07 Maximum

Speed

Search Current

30~150% 110

08-08 BB

speed

search

method

00: Trace from top downward
01: Trace from bottom upward

00

08-09

Auto Restart Times
after Fault

00~10 00

08-10

Auto Restart Time after
Fault

00 to 60000 sec

600