Chapter 4 Parameters|

4-20

Revision July 2008, EG03, SW V1.06

Emergency Stop by DC Brake

Applications Purpose

Functions

Related

Parameters

High-speed rotors

Emergency stop
without brake
resistor

AC motor drive can use DC brake for
emergency stop when a quick stop is
needed without brake resistor. When
used often, take motor cooling into
consideration.

08-00
08-02
08-03

Over-torque Setting

Applications Purpose

Functions

Related

Parameters

Pumps, fans and
extruders

To protect
machines and to
have continuous/
reliable operation

The over-torque detection level can be
set. Once OC stall, OV stall and over-
torque occurs, the output frequency
will be adjusted automatically. It is
suitable for machines like fans and
pumps that require continuous
operation.

06-03~06-05

Upper/Lower Limit Frequency

Applications Purpose

Functions

Related

Parameters

Pump and fan

Control the motor
speed within
upper/lower limit

When user cannot provide
upper/lower limit, gain or bias from
external signal, it can be set
individually in AC motor drive.

01-07
01-08

Skip Frequency Setting

Applications Purpose

Functions

Related

Parameters

Pumps and fans

To prevent
machine vibrations

The AC motor drive cannot run at
constant speed in the skip frequency
range. Three skip frequency ranges
can be set. It is used to smooth
vibration at certain frequencies.

08-11~08-16

Carrier Frequency Setting

Applications Purpose

Functions

Related

Parameters

General application

Low noise

The carrier frequency can be
increased when required to reduce
motor noise.

02-03