Chapter 4 Parameters|

4-12

Revision July 2008, EG03, SW V1.06

Parameter

Functions

Settings

Factory

Setting

Customer

06-06 Electronic

Thermal

Relay Selection

00: Operate disabled.
01: Operate with a standard motor.
02: Operate with a special motor.

02

06-07 Electronic

Thermal

Characteristic

30~600 Sec

60

06-08

Low Current Detection
Level

00~100% (00 disabled)

00

06-09

Low Current Detection
Time

0.1~ 3600.0 Sec

10.0

06-10

Low Current Detection
Treatment

00: Warn and Ramp to stop
01: Warn and Coast to stop
02: Warn and keep operating

01

06-11

Present Fault Record

00

06-12

Second Most Recent
Fault Record

00

06-13 Third Most Recent

Fault Record

00

06-14

Fourth Recent Fault
Record

00: No Fault
01: Oc (over-current)
02: Ov (over-voltage)
03: OH (over temperature)
04: OL (over load)
05: oL1 (over load 1)
06: EF (external fault)
07: Occ (IGBT module is abnormal)
08: CF3 (driver’s internal circuitry is

abnormal)

09: HPF (hardware protection failure)
10: OcA (over-current during acceleration)
11: Ocd (over-current during deceleration)
12: Ocn (over-current during steady state

operation)

13: GFF(Ground Fault)
14: Lv (Low voltage)
15: CF1 (CPU READ failure)
16: CF2 (CPU WRITE failure)
17: bb (Base Block)
18: OL2 (over load2)
19: Reserved
20: Code (software/password protection)
21: EF1 (Emergency stop)
22: PHL (phase-loss)
23: Lc (Low Current)
24: FbL(Feedback Loss)
25: Reserved
26: FANP (Fan Power Fault)
27: FF1 (Fan 1 Fault)
28: FF2 (Fan 2 Fault)
29: FF3 (Fan 3 Fault)
30: FF123 (Fan 1, 2, 3 Fault)

00