Chapter 4 Parameters|

Revision July 2008, EG03, SW V1.06

4-67

70%

Output voltage

100%

Frequency

Automatic Energy-saving Operation

During the auto energy-saving
operation, it will adjust the output
voltage according to the output
power. The maximum output
voltage can be 30% lower than
the normal output voltage.

08 - 18

Automatic Voltage Regulation (AVR)

Factory Setting: 00

Settings

00: AVR function enabled
01: AVR function disabled
02: AVR function disabled for deceleration

This parameter determines the function of Automatic Voltage Regulation is enabled or

disabled.

This parameter is set to 01: when AVR function is disabled, AC drive will calculate input

voltage by DC Bus value (620VDC). Output voltage will vary by DC Bus varying and may

cause output current insufficiently, over current or oscillation.

This parameter is set to 00: when AVR function is enabled, AC drive will calculate output

voltage by actual voltage value of DC Bus. Output voltage won’t vary by DC Bus varying.

This parameter is set to 02: AC drive will disable AVR function during decelerate to stop. It can

speed up braking in some degree.

08 - 19

Software Setting of the Braking Level

(the action level of the braking resistor)

Unit: 0.1

Settings

740.0V~820.0VDC
00: Disabled

Factory Setting: 760.0

This parameter determines software setting of the braking level.

The model VFD055~150F43A has braking chip, user could select suitable braking resistor to

have the best deceleration characteristics.

The action level of the braking resistor could be set by this parameter.