Chapter 4 Parameters|

Revision July 2008, EG03, SW V1.06

4-15

Parameter

Functions

Settings

Factory

Setting

Customer

08-11 Operation

Frequency

Inhibition 1 UP

0.00~160.00 Hz

0.00

08-12 Operation

Frequency

Inhibition 1 DOWN

0.00~160.00 Hz

0.00

08-13 Operation

Frequency

Inhibition 2 UP

0.00~160.00 Hz

0.00

08-14 Operation

Frequency

Inhibition 2 DOWN

0.00~160.00 Hz

0.00

08-15 Operation

Frequency

Inhibition 3 UP

0.00~160.00 Hz

0.00

08-16 Operation

Frequency

Inhibition 3 DOWN

0.00~160.00 Hz

0.00

08-17 Automatic

Energy-

saving

00: Energy-saving operation disabled
01: Energy-saving operation enabled

00

08-18 Automatic

Voltage

Regulation (AVR)

00: AVR function enabled
01: AVR function disabled
02: AVR function disabled for deceleration

00

08-19 Software Setting of the

Braking Level (the
action level of the
braking resistor)

740V~820VDC
00:Disabled

760

08-20 Vibration

Compensation Factor

00~1000 00

Group 9 Communication Parameters

Parameter

Functions

Settings

Factory

Setting

Customer

09-00 Communication

Address

01-254
00:Disabled

01

09-01 Transmission

Speed

(Baud Rate)

00: Baud rate 4800
01: Baud rate 9600
02: Baud rate 19200
03: Baud rate 38400

01

09-02 Transmission

Fault

Treatment

00: Warn and keep operating
01: Warn and RAMP to stop
02: Warn and COAST to stop
03: No warning and no display

03

09-03 Over

Time

Detection

during Transmission

00: Disabled
01: Enabled

00

09-04 Communication

Format

00: 7-bit for ASCII
01: 8-bit for ASCII
02: 8-bit for RTU

00