Group 9: Communication Parameters

09 - 00

Communication Address

Factory Setting: 01

Settings

01-254
00: Disabled

If the AC drive is controlled by RS-485 serial communication, the communication address for

this drive must be set via this parameter.

09 - 01

Transmission Speed (Baud Rate)

Factory Setting: 01

Settings

00: Baud rate 4800
01: Baud rate 9600
02: Baud rate 19200
03: Baud rate 38400

This parameter determines transmission speed of AC drive communication.

09 - 02

Transmission Fault Treatment

Factory Setting: 03

Settings

00: Warn and keep operating
01: Warn and RAMP to stop
02: Warn and COAST to stop
03: No warning and no display

This parameter is set to detect if an error occurs and take actions.

09 - 03

Time-out Detection during Transmission

Factory Setting: 00

Settings

00: Disabled
01: Enabled

This parameter is used for ASCII mode. When this parameter is set to 01, indicates that the

time-out detection is enable, the time slot between each character can’t exceed 500 ms.

09 - 04

Communication Format

Factory Setting: 00

Settings

00: 7-bit for ASCII
01: 8-bit for ASCII
02: 8-bit for RTU