Chapter 4 Parameters|

Revision July 2008, EG03, SW V1.06

4-11

Parameter

Functions

Settings

Factory

Setting

Customer

05-20

Time Duration Step 4

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-21

Time Duration Step 5

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-22

Time Duration Step 6

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-23

Time Duration Step 7

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-24

Time Duration Step 8

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-25

Time Duration Step 9

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-26

Time Duration Step 10 0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-27

Time Duration Step 11 0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-28

Time Duration Step 12 0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-29

Time Duration Step 13 0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-30

Time Duration Step 14 0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-31

Time Duration Step 15 0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

05-32

Time Unit Settings

00: 1 Sec
01: 0.1 Sec

00

Group 6 Protection Function Parameters

Parameter

Functions

Settings

Factory

Setting

Customer

06-00 Over-voltage

Stall

Prevention

660.0V~820.0VDC
00: Disabled

780.0

06-01 Over-current

Stall

Prevention during
Acceleration

20~250%
00: Disabled

150%

06-02 Over-current

Stall

Prevention during
operation

20~250%
00: Disabled

150%

06-03 Over-torque

Detection

Selection

00: Over-torque detection disabled.
01: Over-torque detection enabled during

constant speed operation (OL2), and
operation continues.

02: Over-torque detection enabled during

constant speed operation (OL2), and
operation halted.

03: Over-torque detection enabled during

operation (OL2), and operation
continues.

04: Over-torque detection enabled during

operation (OL2), and operation halted.

00

06-04 Over-torque

Detection

Level

30~150% 110

06-05 Over-torque

Detection

Time

0.1~60.0 Sec

0.1