beautypg.com

Delta Electronics AC Motor Drive VFD-G User Manual

Page 124

background image

Chapter 4 Parameters|

Revision July 2008, EG03, SW V1.06

4-73

™

(8 , E , 1 : 9-04=1 or 2, 9-05=04)

0

1

2

3

4

5

6

7

Start

bit

Even

parity

Stop

bit

8-bit character

11-bit character frame

™

(8, O, 1: 9-04=1 or 2, 9-05=05)

0

1

2

3

4

5

6

7

Start

bit

Odd

parity

Stop

bit

8-bit character

11-bit character frame

3. Communication

Protocol

3.1 Communication Data Frame:

ASCII mode:

STX

Start character ‘:’ (3AH)

ADR 1

ADR 0

Communication address:
8-bit address consists of 2 ASCII codes

CMD 1

CMD 0

Command code:
8-bit command consists of 2 ASCII codes

DATA (n-1)

…….

DATA 0

Contents of data:
N X 8-bit data consists of 2n ASCII codes.
n<=25, maximum of 50 ASCII codes

LRC CHK 1
LRC CHK 0

LRC check sum:
8-bit check sum consists of 2 ASCII codes

END 1

END 0

End characters:
END1= CR (0DH), END0= LF(0AH)

RTU mode:

START

A silent interval of more than 10 ms

ADR

Communication address: 8-bit address

CMD

Command code: 8-bit command

DATA (n-1)

…….

DATA 0

Contents of data:
N X 8-bit data, n<=25

CRC CHK Low

CRC CHK High

CRC check sum:
16-bit check sum consists of 2 8-bit characters

END

A silent interval of more than 10 ms