Echelon IzoT Commissioning Tool User Manual
Page 170

is reset
. For a device to be disabled, it must contain a Node Object
functional block. If Disable is selected and the device does not
contain a Node Object, the device is placed offline. As with
offline operation, portions of a disabled device’s application may
continue to function.
Source of CP
Values
Specify the source of initial values for the device’s configuration
properties.
• OpenLNS Database. The current configuration property values
stored in the OpenLNS network database will be written to the
device.
• Default. The default configuration property values stored in the
device template will be written to the device. This option requires
a device template based on a version 4 or higher XIF file with
specified default values. See the L
ON
M
ARK
Device Interface File
Developer’s Guide on the LonMark Web site for more information
This is the default.
If you select Default, select whether network variable type
configuration properties (SCPTnvType) are restored to their
default values when the device is commissioned. If you want them
to be restored, select the Include NV Type CPs check box. This
check box is cleared by default. This operation will not work if
any of the affected network variables are connected.
• Current Device Values. The current configuration property
values set in the device will be written to the OpenLNS network
database.
This option is only available if you cleared the check box to load
an application image into the device in the Device Application
Image window.
• Application Image File. The current configuration property
values in the selected application image file will be written to the
device.
This option is only available if you selected the check box to load
an application image into the device in the Device Application
Image window.
Device Specific
CPs
Select how device-specific configuration properties are managed when
a device is commissioned.
• Do Not Update. Device-specific configuration properties will not
be modified in the device or the OpenLNS network database. This
is the default.
• Update with Other CPs. The device-specific configuration
property values will be set based on the option selected in the
Source of CP Values box. For example, if you select OpenLNS
Database in the Source of CP Values box, the device-specific
configuration property values stored in the OpenLNS network
database will be written to the device.
• Upload from Device. The current device-specific configuration
property values stored in the device will be written to the
OpenLNS network database.
This option is only available if you cleared the check box to load
an application image into the device in the Device Application
154
Installing Networks