Analog output scaling, Analog output scaling -27 – KEYENCE IL Series User Manual
Page 81
4-2 Basic Settings and Advanced Settings
4-27
IL-E
4
Setting V
ar
iou
s F
unct
ions
The analog output scaling for the judgment value (P.V.) is set.
If the analog output is set to no output, this screen is skipped.
“3-1 Operation When the Power is Turned on for the First Time” (page 3-2)
“3-3 Initial Reset (Initialize)” (page 3-8)
Relation of voltage and analog output in default state (dEFLt)
The upper and lower limits for the different selections of analog outputs are as follows.
10. Analog Output Scaling
#P)
Analog output
Description
Default
value
Default setting
Scaling is not performed.
c
Free range
Scaling is performed. The analog output range can be
changed by specifying the upper limit and lower limit of the
judgment value (P.V.).
Bank
A different scaling is provided for each bank. The analog
output range can be changed by designating an upper
limit and lower limit for each bank.
Example 1: Lower limit < Upper limit
(Analog output 1 to 5 V)
Example 2: Lower limit > Upper limit
(Analog output 1 to 5 V)
Reference
If Upper limit = Lower limit is set, the analog output is output as below.
Judgment value (P.V.)
≤ Upper limit: Analog output lower limit (When 1 to 5 V → 1 V)
Judgment value (P.V.)
> Upper limit: Analog output upper limit (When 1 to 5 V → 5 V)
Lower limit Upper limit
5
1
Output upper
limit
Output lower
limit
Judgment
value
(P.V.)
(V)
(V)
5
1
Lower limit Upper limit
Judgment
value
(P.V.)
Output upper
limit
Output lower
limit
Model
Upper limit
Lower limit
IL-S025
5.000
- 5.000
IL-030
5.000
- 5.000
IL-S065/IL-065
10.000
- 10.000
IL-100
20.000
- 20.000
IL-300
140.00
- 140.00
IL-600
400.00
- 400.00
IL-2000
1000.0
-1000.0
Analog setting
Output upper limit
Output lower limit
OFF
Not output
0-5v
5 V
0 V
-5-5v
5 V
- 5 V
1-5v
5 V
1 V
AMPr
20 mA
4 mA