4-2 Basic Settings and Advanced Settings
4-14
4
Setting V
ar
iou
s F
unct
ions
IL-E
According to the judgment value (P.V.), set the output state (N.O./N.C.) of judgment output
ON/OFF and edge check output.
There are three judgment outputs as below.
• HIGH judgment output (Black wire)
• GO judgment output (Gray wire)
• LOW judgment output (White wire)
The judgment output is turned ON/OFF as below according to the tolerance setting value.
“3-4 Setting the Tolerance Setting Value” (page 3-10)
When Normally Open is set
When Normally Closed is set
*1
"Error Displays and Corrective Actions" (page A-4)
*2 When the judgment value (P.V.) is "-----".
5. Output State
QWV
Item
Setting range
Default value
Output state
no
(Normally Open), nC (Normally Closed)
no
Judgment
Judgment output
HIGH
GO
LOW
HIGH
ON
OFF
OFF
GO
OFF
ON
OFF
LOW
OFF
OFF
ON
Error
*1
ON
OFF
ON
"-----"
*2
OFF
OFF
OFF
Judgment
Judgment output
HIGH
GO
LOW
HIGH
OFF
ON
ON
GO
ON
OFF
ON
LOW
ON
ON
OFF
Error
*1
OFF
ON
OFF
"-----"
*2
ON
ON
ON
Reference
Regardless of the output state setting, the judgment indicator on the sensor
amplifier interlocks the judgment output when Normally Open is set.
“3-4 Setting the Tolerance Setting Value” (page 3-10)
The following is the default state of the judgment indicator. The lighting
status can be changed in the items for "18. Display Color".
"18. Display Color" (page 4-41)
Judgment
Judgment output
HIGH
GO
LOW
HIGH
Red
OFF
OFF
GO
OFF
Green
OFF
LOW
OFF
OFF
Red
Error
Red
OFF
Red
"-----"
OFF
OFF
OFF