beautypg.com

Other information you may need, Fresh air support – Dell PowerEdge C6220 User Manual

Page 53

background image

About Your System | 53


Other Information You May Need

WARNING: See the safety and regulatory information that shipped with your
system. Warranty information may be included within this document or as a
separate document.

The

Getting Started Guide

provides an overview of rack installation, system

features, setting up your system, and technical specifications.

NOTE: Always check for updates on support.dell.com/manuals and read the

updates first because they often supersede information in other documents.

Fresh Air Support

Expanded Operating Temperature

10% of annual
operating hours

5 °C to 40 °C, 5% to 85% RH with 26 °C max. dew point.
For temperatures between 35 °C and 40 °C, de-rate maximum
allowable dry bulb temperature by 1 °C/175 meters above 950
meters (1 °F per 319 feet).

1% of annual
operating hours

–5 °C to 45 °C, 5% to 90% RH with 26 °C dew point.
For temperatures between 40 °C and 45 °C, de-rate maximum
allowable dry bulb temperature by 1 °C/125 meters above 950
meters (1 °F per 228 feet).
NOTE: When operating in the expanded temperature range,
ambient temperature warnings may be reported in the System
Event Log.
NOTE: No cold start up below 5 °C.
NOTE: The operating temperature specification is for a
maximum altitude of 3050 meters (10,000 feet).
NOTE: 1U and 2U nodes support the 130W (8 core),
130W (4 core) and 135W processors with the specific
configurations of HDD, PCI-E and Mezzanine card.
Please refer to the following statements and matrixes of
Fresh Air Support for details.

The numbers of HDD in the tables below list the total
quantity supported per chassis.

No GPU support.