[Run/Accel Boost] – Firmware below 4.01
Sets the percentage of Auto Boost that is applied to
the motor during constant speed or decel. If Auto
Boost is selected in the [DC Boost Select]
parameter (see preceding page), boost is applied as
shown in the adjacent chart.
Parameter Number
169
Parameter Type
Read and Write
Display Units / Drive Units
1%
Factory Default
100%
Minimum Value
0%
Maximum Value
100%
Drive Mode
Auto Boost Applied
Accelerating
Programmed Auto Boost %
Constant Speed
Programmed Auto Boost % x [Run/Accel Boost]
Decelerating
Programmed Auto Boost % x [Run/Accel Boost]
[PWM Frequency]
This parameter sets the carrier frequency for the
sine coded PWM output waveform.
This parameter cannot be changed while the drive is
running.
Refer to page 1–1 for Frame Reference information
and the Derating Guidelines in Appendix A.
Parameter Number
45
Parameter Type
Read and Write
Display Units / Drive Units
2 KHz / KHz/2
Factory Default
Based on drive type
Minimum Value
2 KHz
Maximum Value
A Frame Drives = 10 kHz
B Frame Drives = 8 kHz
C Frame Drives & Up = 6 kHz
[Analog Invert] – Firmware below 4.01
This parameter enables the inverting function for the
analog input signal at TB2.
This parameter cannot be changed while the drive is
running.
Parameter Number
84
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
Analog Invert
Drive Output
Frequency
Maximum
Speed
Minimum
Frequency
0
V
4 mA
10
V
20
mA
Disab
led
Ena
bled
Analog Input Signal
[Analog Trim En]
This parameter enables the pot terminals at TB2,
terminals 1, 2 & 3 as a trim function to the analog
inputs at TB2 terminals 4 & 5 or 4 & 6. A 10k ohm
pot provides a trim range of approximately 10% of
[Maximum Freq]. Drive status must be “Stopped”
before programming changes will take effect.
Parameter Number
90
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
Advanced Setup