Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 86

background image

5–8

Programming

[4-20 mA Hertz]

This parameter displays the frequency command
present at analog current input terminals 4 & 6 of
TB2. This value is displayed whether or not this is
the active frequency command.

Parameter Number

140

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[0-10 Volt Hertz]

This parameter displays the frequency command
present at analog voltage input terminals 4 & 5 of
TB2. This value is displayed whether or not this is
the active frequency command.

Parameter Number

139

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[Pot Hertz]

This parameter displays the frequency command
present at remote pot terminals 1, 2 & 3 of TB2.
This value is displayed whether or not this is the
active frequency command.

Parameter Number

138

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[Pulse/Enc Hertz]

This parameter displays the frequency command
present at pulse input terminals 7 & 8 of TB2 or at
the encoder input terminals on TB3 (if present). This
value is displayed whether or not this is the active
frequency command.

Parameter Number

63

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[MOP Hertz]

This parameter displays the frequency command
from the MOP. The MOP frequency command can
be adjusted by TB3 (if present) and an appropriate
[Input Mode] is selected (see Input Mode Selection
figure in Chapter 2). Some SCANport adapters,
including the RIO Adapter, can also adjust the MOP
frequency command. This value is displayed
whether or not this is the active frequency
command.

Parameter Number

137

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[Heatsink Temp]

This parameter displays the heatsink temperature.

Parameter Number

70

Parameter Type

Read Only

Display Units / Drive Units

1

°

C / Deg. C

Factory Default

None

Minimum Value

0

Maximum Value

255

°

C

Metering