beautypg.com

Appendix c, Ce conformity, Appendix – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 175

background image

Appendix

C

CE Conformity

Low Voltage Directive

The following low voltage directives apply:

EN 60204-1

PREN 50178

EMC Directive

This apparatus is tested to meet Council Directive 89/336
Electromagnetic Compatibility (EMC) using a technical construction
file and the following standards:

EN 50081–1, –2 – Generic Emission Standard

EN 50082–1, –2 – Generic Immunity Standard

Declarations of Conformity to the European Union Directives are
available. Please contact your Allen-Bradley Sales Representative.

Marked for all applicable directives

1

Emissions

EN 50081-1
EN 50081-2
EN 55011 Class A
EN 55011 Class B

Immunity

EN 50082-1
EN 50082-2
IEC 801-1, 2, 3, 4, 6, 8 per EN50082-1, 2

1

Note: Installation guidelines stated below must be adhered to.

Important: The conformity of the drive and filter to any standard does

not guarantee that the entire installation will conform.
Many other factors can influence the total installation and
only direct measurements can verify total conformity.

The following six items are required for CE conformance:

1. Standard 1336 PLUS Drive 0.37-448 kW (0.5-600 HP) CE compat-

ible (Series D or higher).

2. Factory installed EMC enclosure (-AE option) or field installed EMC

Enclosure Kit (1336x-AEx – see page C–2).

3. Filter as called out on the following page.

4. Grounding as shown on page C–3.

5. Input power (source to filter) and output power (filter to drive &

drive to motor) wiring must be braided, shielded cable with a cov-
erage of 75% or better, metal conduit or other with equivalent or
better attenuation, mounted with appropriate connectors. For
shielded cable it is recommended to use a compact strain relief con-
nector with double saddle clamp for filter and drive input and com-
pact strain relief connector with EMI protection for motor output.

6. Control (I/O) and signal wiring must be in conduit or have

shielding with equivalent attenuation.

Requirements for