beautypg.com

Analog out sel, Anlg out offset, Set anlg out lo] –firmware 4.01 & later – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 106: Set anlg out hi] –firmware 4.01 & later

background image

5–28

Programming

[Analog Out Sel]

This parameter selects the source that will drive the
analog output. This output is intended for metering
only and should not be used as process control
feedback.

Important: Firmware versions below 4.01 will have
fewer selections available.

Parameter Number

25

Parameter Type

Read and Write

Factory Default

“Frequency”

Units

Display Drive

“Frequency” 0

Zero to programmed [Maximum Freq]

“Current” 1

Zero to 200%

“Torque” 2

Zero to 200%

“Power” 3

Zero to 200%

“Voltage” 4

Zero to 200%

“% Motor OL” 5

Zero to 200%

“% Drive OL” 6

Zero to 200%

“Encoder” 7

See [Pulse/Enc Hertz]

“Speed Error” 8

See [Speed Error]

“PI Reference” 9

See [PI Reference]

“PI Feedback” 10

See [PI Feedback]

“PI Error” 11

See [PI Error]

“PI Output” 12

See [PI Output]

[Anlg Out Offset]

This parameter enables the voltage or current offset
for the analog output TB2 terminals 4 & 9. This
internal value offsets 0-20mA to 4-20mA and
0-10V to 2-10V.

Parameter Number

154

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

Drive Output

Frequency

Maximum

Speed

Minimum

Frequency

0

V

0

mA

Offset

10

V

20

mA

Analog Output Signal

2

V

4

mA

Analog Out Offset

[Abs Analog Out] –Firmware 4.01 & later

This parameter selects whether a signed value or
absolute value is used for analog out.

Parameter Number

233

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[Set Anlg Out Lo] –Firmware 4.01 & later

Sets the percentage of the [Analog Out Sel] value
that equals 0V/0 mA output.

Parameter Number

234

Parameter Type

Read and Write

Display Units / Drive Units

0.1 % / 4096 = 100%

Factory Default

0.0 %

Minimum Value

–300.0 %

Maximum Value

+300.0 %

[Set Anlg Out Hi] –Firmware 4.01 & later

Sets the percentage of the [Analog Out Sel] value
that equals 10V/20 mA output.

Parameter Number

235

Parameter Type

Read and Write

Display Units / Drive Units

0.1 % / 4096 = 100%

Factory Default

100.0 %

Minimum Value

–300.0 %

Maximum Value

+300.0 %

I/O Config