beautypg.com

Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 102

background image

5–24

Programming

[Language]

This parameter selects between English and the
alternate language for the HIM display.

Parameter Number

47

Parameter Type

Read and Write

Factory Default

“English”

Units

Display Drive

“English” 0

“Alternate” 1

[Speed Control]

This parameter is now located earlier in this group (effective with firmware version 4.01).
Refer to page 5–22 for parameter description.

[Flying Start En]

This value enables the flying start function and
chooses the method to be used. The drive will first
search from the direction it was last running.

Parameter Number

155

Parameter Type

Read and Write

Factory Default

Disabled

Units

Display Drive

“Disabled” 0

“Speed Search” 1

Freq. sweep –see [FStart For./Rev.]

“Use Encoder” 2

Requires feedback encoder

“Track Volts” 3

Read back EMF from sync. p.m.
motor

ATTENTION: The “Speed Search” selection should not be
used with synchronous or permanent magnet motors. Motors
may be demagnetized during braking.

!

[FStart Forward]

This value sets the frequency at which the forward
speed search begins. If this value exceeds
[Maximum Freq], speed search will begin at
[Maximum Freq]. Forward search ends at zero Hertz
or when motor speed is found.

Parameter Number

156

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz

Factory Default

60 Hz

Minimum Value

0 Hz

Maximum Value

400 Hz

[FStart Reverse]

This value sets the frequency at which the reverse
speed search begins. If this value exceeds
[Maximum Freq], speed search will begin at
[Maximum Freq]. Reverse search ends at zero Hertz
or when motor speed is found.

Parameter Number

157

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz

Factory Default

0 Hz

Minimum Value

0 Hz

Maximum Value

400 Hz

[LLoss Restart] – Firmware 4.01 & later

This parameter selects the reconnect mode after
recovery from a line loss condition.

Parameter Number

228

Parameter Type

Read and Write

Factory Default

“Track Volts”

Units

Display Drive

“Speed Search” 1

Frequency sweep

“Use Encoder” 2

Read feedback

“Track Volts” 3

Read motor volts

“Last Speed” 4

Start at last output

Feature Select