5–12

Programming

[Current Lmt Sel]– Firmware 4.01 & later

Selects the source of the [Current Limit] setting for
the drive. When an external input is selected (0-10V
or 4-20 mA), the minimum signal (0V or 4 mA) sets
20% current limit and the maximum signal (10V or
20mA) sets the value programmed in [Current Limit].

This parameter cannot be changed while the drive is
running.

Parameter Number

232

Parameter Type

Read and Write

Factory Default

“Current Lmt”

Units

Display Drive

“Current Lmt” 0

Use [Current Limit], param. 36.

“0-10 Volt” 1

Adjustable through 10V input, TB2,
4 & 5.

“4-20 mA” 2

Adjustable through 4-20mA input,
TB2, 4 & 6.

[Adaptive I Lim] – Firmware 4.01 & later

When ENABLED, this parameter maintains normal
current limit control to provide normal acceleration
into medium to high system inertia.

When DISABLED, this parameter applies a feed
forward command to acceleration, allowing quicker
accel times from stopped to commanded speed with
low system inertia

.

Parameter Number

227

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[Overload Mode]

This parameter selects the derating factor for the I

2

T

electronic overload function. Motors designed to
operate with wider speed ranges need less overload
derating.

Parameter Number

37

Parameter Type

Read and Write

Factory Default

“No Derate” (“Max Derate” frn < 4.01)

Units

Display Drive

“Max Derate” 2

2:1 Speed Range Derate below
50% of Base Speed

“Min Derate” 1

4:1 Speed Range. Derate below
25% of Base Speed

“No Derate” 0

10:1 Speed Range. No Derating

Min Derate

0

80

100

60

40

20

% of Load

% of Load

% of Load

No Derate

0

80

100

60

40

20

% of Base Speed

Max Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

Overload Patterns

1

10

1

10

100

1000

Time to Trip vs. Current (Firmware 4.01 & Up)

Multiple of [Overload Amps]

T

ime to T

rip - Seconds

115%

Cold

Hot

Setup