Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 124
![background image](/manuals/578398/124/background.png)
5–46
Programming
[Speed KI]
This parameter contains the integral gain value for
the velocity loop during closed loop operation.
Parameter Number
165
Parameter Type
Read and Write
Display Units / Drive Units
Numeric / Gain x 100
Factory Default
100
Minimum Value
0
Maximum Value
20000
[Speed Error]
This parameter displays the difference between
[Freq Command] and feedback speed.
Parameter Number
166
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq.
Factory Default
None
Minimum Value
– 8.33% of [Base Frequency]
Maximum Value
+ 8.33% of [Base Frequency]
[Speed Integral]
This parameter displays the integral value from the
speed loop.
Parameter Number
167
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq.
Factory Default
None
Minimum Value
–8.33% of [Base Frequency]
Maximum Value
+ 8.33% of [Base Frequency]
[Speed Adder]
This parameter displays the amount of correction
applied to the [Freq Command].
Parameter Number
168
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq.
Factory Default
None
Minimum Value
– 8.33% of [Base Frequency]
Maximum Value
+ 8.33% of [Base Frequency]
[Motor NP RPM]
This value should be set to the motor nameplate
rated RPM.
This parameter cannot be changed while the drive is
running.
Parameter Number
177
Parameter Type
Read and Write
Display Units / Drive Units
1 RPM / RPM x 10 (x 1 frn < 4.01)
Factory Default
1750 RPM
Minimum Value
60 RPM
Maximum Value
24000 RPM
[Motor NP Hertz]
This value should be set to the motor nameplate
rated frequency.
This parameter cannot be changed while the drive is
running.
Parameter Number
178
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz x 10 (x 1 frn < 4.01)
Factory Default
60 Hz
Minimum Value
1 Hz
Maximum Value
400 Hz
[Pulse/Enc Hertz]
This parameter displays the frequency command
present at pulse input terminals 7 & 8 of TB2 or at
the encoder input terminals on TB3 (if present). This
value is displayed whether or not this is the active
frequency command.
Parameter Number
63
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq
Factory Default
None
Minimum Value
0.00 Hz
Maximum Value
400.00 Hz
Encoder Feedback