Latched alarms, Input status, Freq source – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 113: Freq command, Drive direction
5–35
Programming
[Latched Alarms]
This parameter “stores” the [Drive
Alarm] indications (see above). Bits
will remain set (high/1), even if the
alarm condition no longer exists.
The bit(s) must be programmed to
zero to release the stored
indications.
With drive software versions above
2.00 and a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number
205
Parameter Type
Read Only
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor Stalled
Ground Warning
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Mtr Overload
Unused
Bit 14
Hardware Current Limit
Motoring Current Limit
Motor OL Trip
Auto Reset
Voltage Check
Heatsink Temp
Auxiliary Input
4-20 mA Loss
[Input Status]
This parameter displays the on/off status of inputs
1-8 at TB3 if an optional interface card is installed.
With drive software versions above 2.00 and a
Series A (version 3.0) or Series B HIM, a Status
description (bit ENUM) is displayed on line 1.
Parameter Number
55
Parameter Type
Read Only
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Input 1 – TB3-19
Input 2 – TB3-20
Input 4 – TB3-23
Input 3 – TB3-22
Input 5 – TB3-24
Input 6 – TB3-26
Input 8 – TB3-28
Input 7 – TB3-27
[Freq Source]
This parameter displays the frequency source
currently commanding the drive.
Parameter Number
62
Parameter Type
Read Only
Factory Default
None
Units
Display Drive
“Adapter 1-6” 6-11
“Preset 1-7” 12-18
“Use Last” 0
“Remote Pot” 1
“0-10 Volt” 2
“4-20 mA” 3
“Pulse Ref” 4
“MOP” 5
[Freq Command]
This parameter displays the frequency that the drive
is commanded to output. This command may come
from any one of the frequency sources selected by
[Freq Select 1] or [Freq Select 2].
Parameter Number
65
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq Forward
Factory Default
None
Minimum Value
–400.00 Hz
Maximum Value
+ 400.00 Hz
[Drive Direction]
This parameter displays the commanded running
direction.
Parameter Number
69
Parameter Type
Read Only
Factory Default
None
Units
Display Drive
“Forward” 0
“Reverse” 1
Diagnostics