beautypg.com

Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 109

background image

5–31

Programming

[Blwn Fuse Flt]

Enabling this parameter will allow monitoring of the
bus fuse (in 30 kW/40 HP and up drives) and cause
a “Blwn Fuse Flt.”

Parameter Number

81

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

No Fault Generated

“Enabled” 1

Blwn Fuse Flt Generated

[Low Bus Fault]

This parameter enables or disables the drive fault
condition for bus voltage below the Bus
Undervoltage Trip value listed in the Appendix.

Parameter Number

91

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

No Fault Generated

“Enabled” 1

Undervolt Fault Generated

[Fault Data] –Firmware 4.01 & later

This parameter displays fault related parameter
numbers or bit array information. Certain faults
generate additional information to aid fault
diagnosis.

Parameter Number

207

Parameter Type

Read and Write

Display Units / Drive Units

Parameter # / Parameter #

Factory Default

None

Minimum Value

1

Maximum Value

255

[Flt Motor Mode]

This parameter displays the motor mode active at
the time of the last fault.

Parameter Number

143

Parameter Type

Read Only

Factory Default

None

Units

Display Drive

“1” 1

Power up sequence in progress

“2” 2

Motor connected, drive off

“3” 3

DC boost being applied

“4” 4

Motor running at [Dwell Frequency]

“5” 5

Motor accelerating

“6” 6

Motor at command speed

“7” 7

Motor decelerating

“8” 8

Motor coasting

“9” 9

Motor under DC braking

“10” 10

Waiting for fault reset – returns to 0

“11” 11

Start mode

“12” 12

Flying start search enable

“13” 13

Flying start w/encoder in process

Faults