Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 109
5–31
Programming
[Blwn Fuse Flt]
Enabling this parameter will allow monitoring of the
bus fuse (in 30 kW/40 HP and up drives) and cause
a “Blwn Fuse Flt.”
Parameter Number
81
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Blwn Fuse Flt Generated
[Low Bus Fault]
This parameter enables or disables the drive fault
condition for bus voltage below the Bus
Undervoltage Trip value listed in the Appendix.
Parameter Number
91
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Undervolt Fault Generated
[Fault Data] –Firmware 4.01 & later
This parameter displays fault related parameter
numbers or bit array information. Certain faults
generate additional information to aid fault
diagnosis.
Parameter Number
207
Parameter Type
Read and Write
Display Units / Drive Units
Parameter # / Parameter #
Factory Default
None
Minimum Value
1
Maximum Value
255
[Flt Motor Mode]
This parameter displays the motor mode active at
the time of the last fault.
Parameter Number
143
Parameter Type
Read Only
Factory Default
None
Units
Display Drive
“1” 1
Power up sequence in progress
“2” 2
Motor connected, drive off
“3” 3
DC boost being applied
“4” 4
Motor running at [Dwell Frequency]
“5” 5
Motor accelerating
“6” 6
Motor at command speed
“7” 7
Motor decelerating
“8” 8
Motor coasting
“9” 9
Motor under DC braking
“10” 10
Waiting for fault reset – returns to 0
“11” 11
Start mode
“12” 12
Flying start search enable
“13” 13
Flying start w/encoder in process
Faults