[Overload Amps]
This value should be set to the motor nameplate Full
Load Amps (FLA) for 1.15 SF motors. For 1.0 SF
motors the value should be set to 0.9 x nameplate
FLA.
Parameter Number
38
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Amps / 4096 = Rated Amps
Factory Default
115% of Drive Rating
Minimum Value
20% of Drive Rated Amps
Maximum Value
115% of Drive Rated Amps
[VT Scaling]
This parameter scales the drive for VT ampere
ratings.
This parameter cannot be changed while the drive is
running.
Parameter Number
203
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
Disables Variable Torque Scaling
“Enabled” 1
Enables Variable Torque Scaling
[Motor NP RPM]
This value should be set to the motor nameplate
rated RPM.
This parameter cannot be changed while the drive is
running.
Parameter Number
177
Parameter Type
Read and Write
Display Units / Drive Units
1 RPM / 1 RPM
Factory Default
1750 RPM
Minimum Value
60 RPM
Maximum Value
24000 RPM
[Motor NP Hertz]
This value should be set to the motor nameplate
rated frequency.
This parameter cannot be changed while the drive is
running.
Parameter Number
178
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz x 10 (x 1 frn < 4.01)
Factory Default
60 Hz
Minimum Value
1 Hz
Maximum Value
400 Hz
[Motor NP Volts]– Firmware 4.01 & later
This value should be set to the motor nameplate
rated volts.
This parameter cannot be changed while the drive is
running.
Parameter Number
190
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rated Volts
Factory Default
Drive Rated Volts
Minimum Value
0 Volts
Maximum Value
2 x Drive Rated Volts
[Motor NP Amps]– Firmware 4.01 & later
This value should be set to the motor nameplate
rated current.
This parameter cannot be changed while the drive is
running.
Parameter Number
191
Parameter Type
Read and Write
Display Units / Drive Units
1 Amp / 4096 = Drive Rated Amps
Factory Default
Drive Rated Amps
Minimum Value
0 Amps
Maximum Value
2 x Drive Rated Amps