Appendix a, Specifications and supplemental info, Specifications – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 141: Specifications and supplemental information, Appendix, Protection, Environment
Appendix
A
Specifications and
Supplemental Information
Appendix A provides specifications and supplemental information
including a parameter cross reference and derate information.
Protection
200-240V Drive
380-480V Drive
500-600V Drive
AC Input Overvoltage Trip:
285V AC
570V AC
690V AC
AC Input Undervoltage Trip:
138V AC
280V AC
343V AC
Bus Overvoltage Trip:
405V DC
810V DC
975V DC
Bus Undervoltage Trip:
200V DC
400V DC
498V DC
Nominal Bus Voltage:
324V DC
648V DC
810V DC
Heat Sink Thermistor:
Monitored by microprocessor overtemp trip.
Drive Overcurrent Trip
Software Current Limit:
20 to 160% of VT rated current.
Hardware Current Limit:
180 to 250% of VT rated current (dependent on drive rating).
Instantaneous Current Limit:
220 to 300% of VT rated current (dependent on drive rating).
Line transients:
up to 6000 volts peak per IEEE C62.41-1991.
Control Logic Noise Immunity:
Showering arc transients up to 1500 volts peak
2
.
Power Ride-Thru:
15 milliseconds at full load.
Logic Control Ride-Thru:
0.5 seconds minimum, 2 seconds typical.
Ground Fault Trip:
Phase-to-ground on drive output.
Short Circuit Trip:
Phase-to-phase on drive output.
Environment
Altitude:
1000 m (3300 ft) max. without derating.
Ambient Operating Temperature
IP00, Open:
0 to 50 degrees C (32 to 122 degrees F).
IP20, NEMA Type 1 Enclosed:
0 to 40 degrees C (32 to 104 degrees F).
IP54, NEMA Type 12 Enclosed:
0 to 40 degrees C (32 to 104 degrees F).
IP65, NEMA Type 4 Enclosed:
0 to 40 degrees C (32 to 104 degrees F).
Storage Temperature (all constructions):
–40 to 70 degrees C (–40 to 158 degrees F).
Relative Humidity:
5 to 95% non-condensing.
Shock:
15G peak for 11ms duration (
±
1.0ms).
Vibration:
0.006 inches (0.152 mm) displacement, 1G peak.
Agency Certification:
U.L. Listed
CSA Certified
Q
E
T
N
O
C
D
N
I
6
L
6
5
D
E
T
S
IL
Q
E
T
N
O
C
D
N
I
6
L
6
5
D
E
T
S
IL
Marked for all applicable directives
1
Emissions
EN 50081-1
EN 50081-2
EN 55011 Class A
EN 55011 Class B
Immunity
EN 50082-1
EN 50082-2
IEC 801-1, 2, 3, 4, 6, 8 per EN 50082-1, 2
Low Voltage
EN 60204-1
PREN 50178
1
Note: Installation guidelines called out in Appendix C must be adhered to.
2
Excludes Pulse Train Input.
Specifications