Diagnostics [drive status, 2nd drive sts] –frm. 4.01 & later, Drive alarm – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 112
5–34
Programming
This group of parameters contains values that can be helpful in explaining the operation of
the drive. Drive status, direction, control and alarm conditions as well as drive ratings are
included.
Diagnostics
[Drive Status]
This parameter displays the actual
operating condition in binary format.
Bits 0-7 are displayed on lower half
of line 2 on HIM display, while, bits
8-15 are displayed on the upper half
of line 2.
With drive software versions above
2.00 and a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number
59
Parameter Type
Read Only
Enabled
Running
Command Direction
Actual Direction
Accelerating
Decelerating
Faulted
At Speed
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Alarm
0 = Reverse
1 = Forward
0 = Reverse
1 = Forward
Reference
ID
Local
Adapter ID
Reference
15 14 13 12
Freq Select 1
0
0
0
0
Preset Freq 1
0
0
0
1
Preset Freq 2
0
0
1
0
Preset Freq 3
0
0
1
1
Preset Freq 4
0
1
0
0
Preset Freq 5
0
1
0
1
Preset Freq 6
0
1
1
0
Preset Freq 7
0
1
1
1
Freq Select 2
1
0
0
0
Adapter 1
1
0
0
1
Adapter 2
1
0
1
0
Adapter 3
1
0
1
1
Adapter 4
1
1
0
0
Adapter 5
1
1
0
1
Adapter 6
1
1
1
0
Jog Frequency 1
1
1
1
Local
11 10 9
TB3
0
0
0
1
0
0
1
2
0
1
0
3
0
1
1
4
1
0
0
5
1
0
1
6
1
1
0
Unused
1
1
1
Bit 14
[2nd Drive Sts] –Frm. 4.01 & later
This parameter displays the actual operating
condition in binary format.
Bits 0-7 are displayed on lower half of line 2
on HIM display, while, bits 8-15 are displayed
on the upper half of line 2.
With drive software versions above 4.01 and
a Series A (version 3.0) or Series B HIM, a
Status description (bit ENUM) is displayed on
line 1.
Parameter Number
236
Parameter Type
Read Only
At Freq
At Current
At Torque
Current Lmt
Mtr Overload
Line Loss
Drive Ready
Forward Run
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Drive Power
Bit 14
Reverse Run
Braking
Auto Reset
Economize
Unused
[Drive Alarm]
This parameter displays which
alarm condition is present when bit
6 of [Drive Status] is high
(set to 1). Refer to Chapter 6 for
further alarm information.
With drive software versions above
2.00 and a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number
60
Parameter Type
Read Only
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor Stalled
Ground Warning
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Mtr Overload
Unused
Bit 14
Hardware Current Limit
Motoring Current Limit
Motor OL Trip
Auto Reset
Voltage Check
Heatsink Temp
Auxiliary Input
4-20 mA Loss