Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 87

5–9
Programming
[Power OL Count]– Firmware 4.01 & later
Displays the percentage of accumulated I
2
t for the
drive thermal overload protection. Running
continuously above 115% of drive rated amps will
accumulate a value of 100% and generate an
Overtemp Fault (F08).
Parameter Number
84
Parameter Type
Read Only
Display Units / Drive Units
1 % / 4096 = 100%
Factory Default
None
Minimum Value
0%
Maximum Value
200%
[Motor OL Count]– Firmware 4.01 & later
This parameter displays the percentage of
accumulated I
2
t for the motor overload protection.
Running continuously at programmed [Overload
Amps] will accumulate approximately 70%.
Reduction of load will reduce the OL count. 100%
value will generate an Overload Fault (F07).
Parameter Number
202
Parameter Type
Read Only
Display Units / Drive Units
1 % / 4096 = 100%
Factory Default
None
Minimum Value
0%
Maximum Value
200%
[Last Fault]
This parameter displays the last drive fault. It is
updated whenever a new fault occurs.
Parameter Number
4
Parameter Type
Read Only
Display Units / Drive Units
Fault Number / Fault Number
Factory Default
None
Minimum Value
None
Maximum Value
None
[Torque Current]
This parameter displays the amount of current that
is in phase with the fundamental voltage component.
It is the current that is actually producing torque.
Parameter Number
162
Parameter Type
Read Only
Display Units / Drive Units
0.1 Amp / 4096 = Rated Amps (Motoring)
Factory Default
None
Minimum Value
–200% Drive Rating
Maximum Value
+200% Drive Rating
[Flux Current]
This parameter displays the amount of current that
is out of phase with the fundamental voltage
component. It is the current required to maintain
motor flux.
Parameter Number
163
Parameter Type
Read Only
Display Units / Drive Units
0.1 Amp / 4096 = Rated Amps (Motoring)
Factory Default
None
Minimum Value
–200% Drive Rating
Maximum Value
+200% Drive Rating
[% Output Power]
This parameter displays the % output power of the
drive.
Parameter Number
3
Parameter Type
Read Only
Display Units / Drive Units
1 % /
±
4096 =
±
100%
Factory Default
None
Minimum Value
–200% Drive Rated Output Power
Maximum Value
+200% Drive Rated Output Power
[% Output Curr]
This parameter displays the % output current of the
drive.
Parameter Number
2
Parameter Type
Read Only
Display Units / Drive Units
1 % / 4096 = 100%
Factory Default
None
Minimum Value
0%
Maximum Value
200% Rated Drive Output Current
Metering