Fault alarms, Flt clear mode, Ground warning – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 111

background image

5–33

Programming

[Fault Alarms]

This parameter stores and displays
the last alarm conditions present
prior to a fault. Refer to Chapter 6
for further alarm information.

With drive software versions above
2.00 and a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.

Parameter Number

173

Parameter Type

Read Only

Bus Charging

Regenerating Current Limit

Regenerating Voltage Limit

Line Loss In Progress

Motor Stalled

Ground Warning

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9

Bit 8

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Mtr Overload

Unused

Bit 14

Hardware Current Limit

Motoring Current Limit

Motor OL Trip

Auto Reset

Voltage Check

Heatsink Temp

Auxiliary Input

4-20 mA Loss

[Flt Clear Mode]

This parameter controls the method for clearing
faults.

Parameter Number

39

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

Faults cleared only by cycling power

“Enabled” 1

Faults cleared by issuing a valid
stop command (only through
TB3/HIM) or cycling power – refer to
Bit 3 of the Logic Control Structure
on page A–13

[Ground Warning]

Enables the Ground Warning fault when the drive
senses ground current in excess of 2 amperes
(approximate). Refer to Chapter 6 for further
information.

Parameter Number

204

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

No Fault Generated

“Enabled” 1

Ground Warning Generated

Faults