Fault alarms, Flt clear mode, Ground warning – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 111
5–33
Programming
[Fault Alarms]
This parameter stores and displays
the last alarm conditions present
prior to a fault. Refer to Chapter 6
for further alarm information.
With drive software versions above
2.00 and a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number
173
Parameter Type
Read Only
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor Stalled
Ground Warning
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Mtr Overload
Unused
Bit 14
Hardware Current Limit
Motoring Current Limit
Motor OL Trip
Auto Reset
Voltage Check
Heatsink Temp
Auxiliary Input
4-20 mA Loss
[Flt Clear Mode]
This parameter controls the method for clearing
faults.
Parameter Number
39
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
Faults cleared only by cycling power
“Enabled” 1
Faults cleared by issuing a valid
stop command (only through
TB3/HIM) or cycling power – refer to
Bit 3 of the Logic Control Structure
on page A–13
[Ground Warning]
Enables the Ground Warning fault when the drive
senses ground current in excess of 2 amperes
(approximate). Refer to Chapter 6 for further
information.
Parameter Number
204
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Ground Warning Generated
Faults