Control, Input/output ratings – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 142
![background image](/manuals/578398/142/background.png)
A–2
Specifications and Supplemental Information
Electrical
Input Data
Voltage Tolerance:
–10% of minimum, +10% of maximum.
Frequency Tolerance:
48-62 Hz.
Input Phases:
Three-phase input provides full rating for all drives.
Single-phase operation is possible for A & B Frame drives
at a derating of 50%.
Displacement Power Factor
A1-A3 Frame Drives:
0.80 standard, 0.95 with optional inductor.
A4 Frame & Up Drives:
0.95 standard.
Efficiency:
97.5% at rated amps, nominal line volts.
Max. Short Circuit Current Rating: 200,000A rms symmetrical, 600 volts (when used with AC
input line fuses specified in Chapter 2).
Control
Method:
Sine coded PWM with programmable carrier frequency. Ratings
apply to all drives (refer to the Derating Guidelines on page A–5).
A Frame Drives
2-10 kHz. Drive rating based on 4 kHz (see pg. 1–1 for frame info).
B Frame Drives
2-8 kHz. Drive rating based on 4 kHz (see pg. 1–1 for frame info).
C & D Frame Drives
2-6 kHz. Drive rating based on 4 kHz (see pg. 1–1 for frame info).
E Frame Drives & Up
2-6 kHz. Drive rating based on 2 kHz (see pg. 1–1 for frame info).
Output Voltage Range:
0 to rated voltage.
Output Frequency Range:
0 to 400 Hz.
Frequency Accuracy
Digital Input:
Within
±
0.01% of set output frequency.
Analog Input:
Within
±
0.4% of maximum output frequency.
Selectable Motor Control:
Sensorless Vector with full tuning. Standard V/Hz with full custom
capability.
Accel/Decel:
Two independently programmable accel and decel times. Each
time may be programmed from 0 - 3600 seconds
1
in 0.1 second
increments
2
.
Intermittent Overload:
Constant Torque – 150% of rated output for 1 minute.
Variable Torque – 115% of rated output for 1 minute.
Current Limit Capability:
Proactive Current Limit programmable from 20 to 160% of rated
output current. Independently programmable proportional and in-
tegral gain.
Inverse Time Overload Cap. Class 10 protection with speed sensitive response. Investigated by
U.L. to comply with N.E.C. Article 430. U.L. File E59272, volume 4/6.
1
600 seconds with Firmware Versions before 4.01.
2
0.1 second increments using a HIM or 0.01 with serial communications.
Input/Output Ratings
Each 1336 PLUS Drive has constant and variable torque capabilities. The
listings on the next page provide input & output current and kVA ratings.
Note: Drive ratings are at nominal values. See Derating Guidelines
on page A–5.