Device options menu – SATEC PM180 Operation Manual User Manual
Page 40

Chapter 3 Using the RDM
Configuring the PM180
38
PM180 Substation Automation Unit
The following table lists available port options, their default settings and ranges.
Label
Option
Range
Default
Prot
Communications protocol
rtu - MODBUS RTU
ASCII - MODBUS ASCII
dnP3 - DNP3.0
rtu
rS
Port interface
232, 422, 485
232 (COM1)
485 (COM2/3)
Addr
Device address
1-247 (MODBUS)
1-255 (DNP3.0)
1
bAud
Baud rate
300-115200 bps
19200
dAtA
Data format
7E, 8n, 8E
8n
To select a port option:
1. Press SELECT to activate the middle window.
2. Use the Up/Down arrow keys to scroll to the
desired option.
To change the port option:
1. Press SELECT to activate the lower window.
2. Use the Up/Down arrow keys to set the desired option.
3. Press ENTER to confirm your changes and to store your new
setting, or press ESC to discard changes.
To exit the menu:
From the middle window, press ESC or ENTER.
Device Options Menu
This menu allows you to select some user-configurable device options or put the
device into energy test mode. To enter the menu, select “OPtS’ from the menu list.
The following table lists available device options, their default settings and ranges.
Label
Option
Range
Default
Description
P.cAL
Power calculation
mode
rEAc (using reactive power),
nAct (using non-active
power)
rEAc
The method used for calculating
reactive and apparent powers (see
“Power Calculation Modes” in
, Chapter 7)
roLL
Energy roll value
10.E4 = 10,000 kWh
10.E5 = 100,000 kWh
10.E6 = 1,000,000 kWh
10.E7 = 10,000,000 kWh
10.E8 = 100,000,000 kWh
10.E9 =1,000,000,000 kWh
10.E9
The value at which energy counters
roll over to zero
test
Energy test mode OFF, On
OFF
Setting this option to On puts the
device into the energy test mode
To select a menu option:
1. Press SELECT to activate the middle window.
2. Use the Up/Down arrow keys to scroll to the desired option.
To change the option:
1. Press SELECT to activate the lower window.
2. Use the Up/Down arrow keys to set the desired option.
3. Press ENTER to confirm your changes and to store your new
setting, or press ESC to discard changes.
To exit the menu:
From the middle window, press ESC or ENTER.
OPtS
rEAc
P.cAL
SELECT
ENERGY
ENTER
ENERGY
ENTER
CHG
OPtS