Clearing en50160 evaluation counters, Configuring the fault recorder, En50160 harmonics limits setup – SATEC PM180 Operation Manual User Manual
Page 106
![background image](/manuals/572148/106/background.png)
Chapter 8 Configuring Recorders
Configuring the Fault Recorder
104
PM180 Substation Automation Unit
Option
Range
Default
Description
2nd Signaling
Frequency
110-3000 Hz
191.0 Hz
Specifies the mains signaling frequency for the
compliance evaluation
3rd Signaling
Frequency
110-3000 Hz
217.0 Hz
Specifies the mains signaling frequency for the
compliance evaluation
4th Signaling
Frequency
110-3000 Hz
317.0 Hz
Specifies the mains signaling frequency for the
compliance evaluation
Clearing EN50160 Evaluation Counters
To clear the present contents of the EN50160 evaluation counters before starting
your EN50160 evaluation, check the On-line button, select Reset from the Monitor
menu, and then Click on the “Clear EN50160 Counters” button (for more information,
see
Resetting Accumulators and Clearing Log Files
).
Configuring the Fault Recorder
The Fault recorder automatically records all fault events to the Fault log and to the
Sequence-of-Events log files. It can be triggered via the embedded fault detector, or
externally through any of the 48 digital inputs.
The Fault recorder can be globally disabled or enabled in your device.
The Fault recorder setup allows you to adjust thresholds and hysteresis for different
fault triggers, and to define the waveform and data log options for synchronous
recording during the fault events.
To configure the Fault recorder:
1. Select Memory/Log from the Meter Setup menu, and then click on
the Fault Recorder tab.
2. Enable fault triggers suitable for your application. Each one,
except of the external digital triggers, must be individually enabled
for the Fault recorder.
3. If you wish to change the default settings, adjust thresholds and
hysteresis for your fault triggers.
4. Select the waveform and data logging options for fault events.
5. Download your setup to the device.
The following table lists available Fault recorder options: