En50160 harmonics limits setup, En50160 advanced setup – SATEC PM180 Operation Manual User Manual
Page 104

Chapter 8 Configuring Recorders
Configuring the EN50160 Power Quality Recorder
102
PM180 Substation Automation Unit
The power quality fault signal is used for cross triggering multiple recorders through a
dedicated digital input in order to simultaneously record disturbances at different
locations. External triggering of the Waveform and Data recorders for recording
disturbance data is done through a setpoint programmed to monitor the status of a
digital input. For more information on cross triggering, see
EN50160 Harmonics Limits Setup
This setup allows you to adjust compliance limits for harmonic and interharmonic
voltages.
To change the default limits in your device:
1. Select Memory/Log from the Meter Setup menu, and then click on
the EN50160 Harmonics setup tab.
2. Adjust limits you want to change.
3. Download your setup to the device.
The default EM50160 compliance limits are shown in the picture above. You can
change the number of the evaluated harmonics and interharmonics via the
EN50160 Advanced Setup
The EN50160 Advanced Setup allows you to configure the EN50160 evaluation
options in your device.
To configure the EN50160 evaluation options:
1. Select Memory/Log from the Meter Setup menu, and then click on
the EN50160 Advanced Setup tab.
2. Change the EN50160 evaluation options if required.
3. Download your setup to the device.
The default EN50160 evaluation options set in your device are shown in the picture
below.