Power quality display, Energy display – SATEC PM180 Operation Manual User Manual
Page 32
Chapter 3 Using the RDM
Data Display
30
PM180 Substation Automation Unit
Page Label
Parameter
Units LED
Hi
Maximum total kvar
kvar/Mvar
9
Maximum volt demand V1/V12
V1/V1-2 - kV1/kV1-2
Maximum volt demand V2/V23
V2/V2-3 - kV2/kV2-3
Hd
Maximum volt demand V3/V31
V3/V3-1 - kV3/kV3-1
10
Maximum ampere demand I1
A1
Maximum ampere demand I2
A2
Hd
Maximum ampere demand I3
A3
11
Maximum sliding window kVA demand
kVA/MVA
Power factor (import) at maximum kVA demand
PF
Hd
Maximum sliding window kW import demand
kW/MW
Power Quality Display
Press the THD/TDD key. The THD or TDD LED illuminates. Use the UP/DOWN
arrow keys to scroll through harmonics measurements.
The following table lists the available display pages. Note that voltage harmonics
readings are phase-to-neutral in 4LN3 and 3LN3 wiring modes, and phase-to-phase
in all other modes.
Page Label
Parameter
Units LED
1
THD V1/V12
V1/V1-2 - kV1/kV1-2
THD V2/V23
V2/V2-3 - kV2/kV2-3
thd.
THD V3/V31
V3/V3-1 - kV3/kV3-1
2
THD I1
A1
THD I2
A2
thd.
THD I3
A3
3
TDD I1
A1
TDD I2
A2
tdd.
TDD I3
A3
4
K-Factor I1
A1
K-Factor I2
A2
HF
K-Factor I3
A3
5
1
Pst V1/V12
V1/V1-2 - kV1/kV1-2
Pst V2/V23
V2/V2-3 - kV2/kV2-3
PSt
Pst V3/V31
V3/V3-1 - kV3/kV3-1
6
1
Plt V1/V12
V1/V1-2 - kV1/kV1-2
Plt V2/V23
V2/V2-3 - kV2/kV2-3
PLt
Plt V3/V31
V3/V3-1 - kV3/kV3-1
Energy Display
Press the ENERGY key. The MVAh, Mvarh, or MWh LED illuminates. Use the
UP/DOWN arrow keys to scroll through energy measurements.
The following table shows energy display pages.
Page Label
Parameter
Units LED
1
Ac.En.
IP.
MWh import
MWh
2
rE.En.
IP.
Mvarh import
Mvarh
3
AP.En.
MVAh
MVAh
4
Ac.En.
EP.
MWh export
MWh
5
rE.En.