Appendix E Data Scales
PM180 Substation Automation Unit
181
Appendix E Data Scales
The maximum values for volts, amps and power in the PM180 setup and in
communications are limited by the voltage and current scale settings. See
in Chapter 7 on how to change the voltage and current scales in your
device.
The following table shows the device data scales.
Scale
Conditions
Range
Maximum voltage (V max)
All configurations
Voltage scale
PT Ratio, V
1
Maximum current (I max)
All configurations
Current scale
CT Ratio, A
2, 3
Maximum fault current (Ix max)
All configurations
30
CT primary current, A
Maximum Power (P max)
4
All configurations
V max
I max
2, W
Maximum frequency
50 or 60 Hz
100 Hz
1
The default voltage scale is 828V. The recommended voltage scale is
120V+20% = 144V for using with external PT’s, and 690V+20% = 828V for a
direct connection to power line.
2
CT Ratio = CT primary current/CT secondary current
3
The default current scale is 2
CT secondary for the IEC current input option
(2.0A with 1A secondaries and 10.0A with 5A secondaries), and 4
CT
secondary for the ANSI current input option (4.0A with 1A secondaries and
20.0A with 5A secondaries).
4
Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited to
9,999,000 W.