Chapter 3 Using the RDM
Configuring the PM180
34
PM180 Substation Automation Unit
Label
Option
Range
Default
Description
Updt
Update rate
0.1-10.0 sec
1 sec
Defines the interval between display
updates
ScrL
Auto scroll
NONE, 2-15
sec
NONE
Disables auto scroll or defines the scroll
interval for the main data display
rEtn
Auto return to the
main screen
diS, En
diS
Disables or enables auto return to the
main display after 30 seconds of
uninterrupted use
Uolt
Primary/Secondary
volts units
Pri, SEc
Pri
Sets primary or secondary units for volts
display
Ph.P
Phase powers display
mode
diS, En
diS
Disables or enables phase powers in the
main display
Fund.
Fundamental values
display mode
diS, En
diS
Disables or enables fundamental values
in the main display
dAtE
Date order
dnY, ndY, Ynd, ndY
Defines the date order in the RTC display
Addr
Master PM180 device
address
1-247
1
The target PM180 device address (must
match the PM180 COM3 port setting)
bAud
Baud rate
4800-115200
19200
The RDM port baud rate (must match the
PM180 COM3 port setting)
dAtA
Data format
8n
8n
The RDM port data format (must match
the PM180 COM3 port setting)
To select a display option:
1. Press SELECT to activate the middle window.
2. Use the Up/Down arrow keys to scroll to the desired option.
To change the display option:
1. Press SELECT to activate the lower window.
2. Use the Up/Down arrow keys to set the desired option.
3. Press ENTER to confirm your changes and to store your new
setting, or press ESC to discard changes.
To exit the display menu:
From the middle window, press ESC or ENTER.
Configuring the PM180
The RDM allows you to set up only limited number of parameters in
your PM180, such as basic configuration settings and communications
settings for serial ports. All other settings can be made through
HyperTerminal and PAS.
Clock Setup Menu
This menu allows you to set up the device clock and to configure your local time zone
settings.
The following table lists available options.
Label
Option
Format/Range
Default
Description
hour
Time
hh.mm.ss
The time is displayed as hh.mm.ss, where
the hours and minutes are shown in the
middle window separated by a dot, and
the seconds - in the lower window.
E
The letter “E” at left shows that the time is
locked, i.e., is synchronized to the GPS
satellite time
U
The letter “U” at left shows that the time is
unlocked, i.e., the satellite signal was lost
and the GPS receiver runs in
freewheeling mode
hour
E 25.
17.43.
SELECT
ENERGY
ENTER
ENERGY
ENTER
CHG
rtc