Reset menu – SATEC SA300 ezPAC Operation Manual User Manual
Page 41

Chapter 3 Using the RDM
Configuring the SA300
SA300 Substation Automation Unit
41
:
Note
The SA300 uses the same password for all communications ports. The password you enter is
effective for all ports, as well as in HyperTerminal, Telnet and PAS.
Reset Menu
This menu allows you to clear the energy and maximum demand accumulators,
Min/Max log, counters and device diagnostics in your SA300. To enter the Reset
menu, select rESEt from the menu list.
The following table lists available options.
Label Description
A.dnd
Clears maximum ampere demands
P.dnd
Clears maximum power demands
dnd
Clears all maximum demands
Enrg
Clears all total energies
Lo.Hi
Clears Min/Max log
tOU.d
Clears summary and TOU maximum demands
tOU.E
Clears summary and TOU energy registers
Cnt
Clears all counters
Cnt1 - Cn16 Clears counter #1 to #16
diAG
Clears device diagnostics
To reset the desired value:
1. Press SELECT to activate the middle window.
2. Use the Up/Down arrow keys to scroll to the desired option.
3. Press SELECT to activate the lower window.
4. Press and hold the ENTER key for about 5 seconds until the “do”
label is replaced with “done’, and then release the key.
5. Press ESC to quit the menu.
SELECT
ENERGY
ENTER
ENERGY
ENTER
CHG
S
rESEt
rESEt
do
A.dnd