Chapter 3 Using the RDM
Configuring the SA300
40
SA300 Substation Automation Unit
Label Option
Range
Default
Description
P.cAL Power
calculation
mode
rEAc (using reactive power),
nAct (using non-active
power)
rEAc
The method used for calculating
reactive and apparent powers (see
“Power Calculation Modes” in
, Chapter 7)
roLL
Energy roll value 10.E4 = 10,000 kWh
10.E5 = 100,000 kWh
10.E6 = 1,000,000 kWh
10.E7 = 10,000,000 kWh
10.E8 = 100,000,000 kWh
10.E9 =1,000,000,000 kWh
10.E9
The value at which energy counters
roll over to zero
test
Energy test mode OFF, On
OFF
Setting this option to On puts the
device into the energy test mode
To select a menu option:
1. Press SELECT to activate the middle window.
2. Use the Up/Down arrow keys to scroll to the desired option.
To change the option:
1. Press SELECT to activate the lower window.
2. Use the Up/Down arrow keys to set the desired option.
3. Press ENTER to confirm your changes and to store your new
setting, or press ESC to discard changes.
To exit the menu:
From the middle window, press ESC or ENTER.
Access Control Menu
This menu allows you to change the user password and enable or disable the device
security. To enter the menu, select “AccS’ from the menu list.
To select a menu option, use the Up/Down arrow keys to scroll to the desired option.
To change the password:
1. Select “PASS” in the upper window using the Up/Down arrow
keys.
2. Press SELECT to activate the first digit.
3. Set the first digit using the Up/Down arrow keys.
4. Press SELECT to advance to the next digit.
5. Set the other password digits in the same manner.
6. Press ENTER to confirm your changes and to store your new
setting, or press ESC to discard changes.
To enable or disable password protection:
1. Select “CtrL” in the upper window using the Up/Down arrow keys.
2. Press SELECT to activate the lower window.
3. Use the Up/Down arrow keys to set the desired option. Select “On”
to enable security, select “OFF’ to disable password protection.
4. Press ENTER to confirm your changes and to store your new
setting, or press ESC to discard changes.
To exit the menu:
From the upper window, press ESC.
CtrL
OFF
PASS
0000
0000
SELECT
ENERGY
ENTER
ENERGY
ENTER
CHG
S
AccS