Clearing en50160 evaluation counters, Configuring the fault recorder – SATEC SA300 ezPAC Operation Manual User Manual
Page 107

Chapter 8 Configuring Recorders
Configuring the Fault Recorder
SA300 Substation Automation Unit
107
Option Range
Default
Description
Mains Signaling Voltage
Evaluation
Disabled,
Enabled
Disabled
Enables the evaluation of the mains signaling voltages
1st Signaling
Frequency
110-3000 Hz 183.0 Hz Specifies the mains signaling frequency for the
compliance evaluation
2nd Signaling
Frequency
110-3000 Hz 191.0 Hz Specifies the mains signaling frequency for the
compliance evaluation
3rd Signaling
Frequency
110-3000 Hz 217.0 Hz Specifies the mains signaling frequency for the
compliance evaluation
4th Signaling
Frequency
110-3000 Hz 317.0 Hz Specifies the mains signaling frequency for the
compliance evaluation
Clearing EN50160 Evaluation Counters
To clear the present contents of the EN50160 evaluation counters before starting
your EN50160 evaluation, check the On-line button, select Reset from the Monitor
menu, and then Click on the “Clear EN50160 Counters” button (for more information,
see
Resetting Accumulators and Clearing Log Files
).
Configuring the Fault Recorder
The Fault recorder automatically records all fault events to the Fault log and to the
Sequence-of-Events log files. It can be triggered via the embedded fault detector, or
externally through any of the 48 digital inputs.
The Fault recorder can be globally disabled or enabled in your device.
The Fault recorder setup allows you to adjust thresholds and hysteresis for different
fault triggers, and to define the waveform and data log options for synchronous
recording during the fault events.
To configure the Fault recorder:
1. Select Memory/Log from the Meter Setup menu, and then click on
the Fault Recorder tab.
2. Enable fault triggers suitable for your application. Each one,
except of the external digital triggers, must be individually enabled
for the Fault recorder.