Appendix e data scales – SATEC SA300 ezPAC Operation Manual User Manual
Page 181
Appendix E Data Scales
SA300 Substation Automation Unit
181
Appendix E Data Scales
The maximum values for volts, amps and power in the SA300 setup and in
communications are limited by the voltage and current scale settings. See
in Chapter 7 on how to change the voltage and current scales in your
device.
The following table shows the device data scales.
Scale Conditions Range
Maximum voltage (V max)
All configurations
Voltage scale
× PT Ratio, V
1
Maximum current (I max)
All configurations
Current scale
× CT Ratio, A
2, 3
Maximum fault current (Ix max) All configurations
30
× CT primary current, A
Maximum Power (P max)
4
All configurations
V max
× I max × 2, W
Maximum frequency
50 or 60 Hz
100 Hz
1
The default voltage scale is 828V. The recommended voltage scale is 120V+20% = 144V for
using with external PT’s, and 690V+20% = 828V for a direct connection to power line.
2
CT Ratio = CT primary current/CT secondary current
3
The default current scale is 2
× CT secondary for the IEC current input option (2.0A with 1A
secondaries and 10.0A with 5A secondaries), and 4
× CT secondary for the ANSI current input
option (4.0A with 1A secondaries and 20.0A with 5A secondaries).
4
Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited to 9,999,000 W.