Configuring dnp3, Dnp options, Chapter 10 configuring communication protocols – SATEC SA300 ezPAC Operation Manual User Manual
Page 114: Configuring modbus, Modbus point mapping, Changing raw scales for 16-bit registers
Chapter 10 Configuring Communication
Configuring DNP3
114
SA300 Substation Automation Unit
To change the default low and high raw scales:
1. From the Meter Setup menu select Protocol Setup and click on the
Modbus Registers tab.
2. Change the raw scales in the Modbus Options pane. The
allowable range is 0 to 65535.
3. Click Send to download your setup to the device.
Configuring DNP3
DNP Options can be changed both via DNP3 and Modbus. Refer to the SA300 DNP3
Reference guide for information on the protocol implementation and a list of the
available data points.
DNP Options
From the Meter Setup menu select Protocol Setup and click on the DNP Options tab.
The following table describes available DNP options. Refer to the DNP3 Data Object
Library document available from the DNP User’s Group on the DNP3 object types.
Parameter Options Default
Description
Binary Inputs (BI)
Number of BI to
Generate events
0-64
3
21
The total number of BI change event
points for monitoring
Binary Input
Object
Single-bit
With Status
Single-bit
The default BI object variation for
requests with qualifier code 06 when no
specific variation is requested
Binary Input
Change Event
Object
Without Time
With Time
With Time
The default BI change event object
variation for requests with qualifier code
06 when no specific variation is
requested
Analog Inputs (AI)
Number of AI to
Generate events
0-64
3
43
The total number of AI change event
points for monitoring