beautypg.com

8 appendix, Plc functionality, Drive plc – Lenze Global Drive PLC Developer Studio User Manual

Page 81: 8appendix, 1 plc functionality, Appendix

background image

Drive PLC

Appendix

8.1

PLC functionality

8−1

L

DrivePLC DE 6.0

8

Appendix

8.1

PLC functionality

Field

Number Description

Inputs

digital

8 Free inputs (3 of them interruptible)

24 V DC / 8 mA each input

analog

3 Free inputs (10 bit + sign)

±10 V

Outputs

digital

4 Free outputs

24 V DC / max. 1 A each output

analog

1 Free output (10 bit + sign)

±10 V / max. 2 mA

Operation set

According to IEC61131−3

Counter/times

According to IEC61131−3, depending on the data memory available.

Flags

1000 Flag words

Memory

See chapter 8.3 (

^ 8−4)

Processing time (1−bit operation)

1

ms

Task types

8 Time or event−controlled tasks (1 ms ... 16 s)

1 Cyclic task

Programming software

Drive PLC Developer Studio

·

Programming languages according to IEC61131−3 standard (IL, LD, FBD, ST,
SFC) as well as CFC editor

·

Monitoring, visualisation, simulation and debugging