beautypg.com

Analog1_io (node number 11), Inputs_analog1 (analog input), Drive plc – Lenze Global Drive PLC Developer Studio User Manual

Page 34: 6 analog1_io (node number 11), System blocks, 1 inputs_analog1 (analog input)

background image

2.6

ANALOG1_IO (node number 11)

Drive PLC

System blocks

2−20

L

DrivePLC DE 6.0

2.6

ANALOG1_IO (node number 11)

2.6.1

Inputs_ANALOG1 (analog input)

This SB forms the interface for analog signals via terminal AI1, A

^ as setpoint input or actual value

input.

AI1

A

AIN1_nIn_a

Inputs_ANALOG1

C0400/1

Fig. 2−10

Inputs_ANALOG1

System variables

Variable

Data type

Signal type

Address

Display

code

Display

format

Notes

AIN1_nIn_a

Integer

analog

%IW11.0

C0400/1

dec [%]

Analog input 1

Terminal assignment

Terminal

Use

Data

AI1

Analog input 1

Level:
Resolution:
Internal resistance:
Normalisation:

−10 V ... +10 V
10 bits + sign
100 k

W

±10 V º ±16384 º ±100 %

A

^

Internal ground, GND