beautypg.com

Outputs_pwrup, Drive plc, System blocks – Lenze Global Drive PLC Developer Studio User Manual

Page 51: 1 outputs_pwrup

background image

Drive PLC

System blocks

2.13

PWRUP_PowerUpControl (node number 171)

2−37

L

DrivePLC DE 6.0

2.13.1

Outputs_PWRUP

System variables

Variable

Data type

Signal type

Address

Display

code

Display

format

Notes

PWRUP_bWaitFor24V
_b

Bool

binary

%QX171.1.0

TRUE: After initialisation, wait and
see if a sufficient supply voltage is
applied again (>17.5 V)

PWRUP_wMaxDelayTi
meFor24V

WORD

%QW171.0

Maximum waiting time in ms; U15
TRIP is activated unless a supply
voltage of at least 17.5 V is
applied after this time.