6. Diagnostic and error treatment
6−10
Festo P.BE−SPC200−COM−CANDN−EN en 0511a
6.5
Diagnosis of the DeviceNet profile communication
The protocol variant DeviceNet profile also has its own fault
code. The composition of the Response Message in the event
of a fault is as follows:
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Status byte
1
2
Fault code
3
4
Extended fault code
5
6
7
Fault code
Meaning
0
No fault
1
Command Message type not valid
2
Command Axis number not valid
3
Response Message type not valid
4
Command Axis number not valid
7
Parameter fault (see extended fault code)
With fault code 7, there appears an extended fault code
instead of the work data in byte 4 of the Response Message.
Take this into account when programming your PLC/IPC
(ifĂnecessary, end update with RMT = 0).