4. Commissioning
4−11
Festo P.BE−SPC200−COM−CANDN−EN en 0511a
5. Set also the following in this register card:
Setting
Notes
Bus address
0...63. Field bus addresses may only
be assigned once per scanner.
Baud rate
125 kBaud, 250 kBaud or 500 kBaud.
Set the field bus baud rate so that it
matches the setting of your scanner.
I/O configuration
Number of I/O bytes to be
transmitted:
Ĉ Profile mode: always 8 I−bytes and
8 O−bytes.
Ĉ I/O mode with Record Select:
4 I−bytes and 2 O−bytes.
Ĉ I/O mode with Start/Stop:
2...8 I−bytes and 2...8 O−bytes.
(See also the overview of the address
ranges of the field bus module in
section 4.1.3).