Field bus cable, cable lengths and baud rates – Festo Кабели и принадлежности User Manual
Page 33

3. Installation
3−5
Festo P.BE−SPC200−COM−CANDN−EN en 0511a
Field bus cable, cable lengths and baud rates
Please note
·
Ascertain from the manual for your PLC or scanner the
cable types, T−adapters, baud rates and cable lengths
which are permitted.
The following table shows guide values for the maximum
permitted cable lengths if thick cable" is used:
DeviceNet
Baud rate
Main bus
length max.
Branch line
length
maximum
Branch line
length
cumulative
125 kBaud
500 m
6 m
156 m
250 kBaud
250 m
78 m
500 kBaud
100 m
39 m