3. Installation

3−3

Festo P.BE−SPC200−COM−CANDN−EN en 0511a

Warning
Undesired movement of the connected actuators and non−
defined switching states of the electronics can cause injury
to human beings or damage to property.

Before carrying out installation and/or maintenance work,
switch off the following in the sequence specified:

1. the compressed air supply

2. the following power supplies:

Ĉ the load voltage for field devices and proportional

directional control valves (plug X2, pin 1)

Ĉ the load voltage supply for the outputs (plug X6/X8,

pinĂ8)

Ĉ if applicable, the load voltage supply on the axis interĆ

face string

Ĉ the operating voltage supply for the internal electronics

of the SPC200 and field devices (plug X2, pin 2).