4. Commissioning
4−13
Festo P.BE−SPC200−COM−CANDN−EN en 0511a
4.1.3
I/O address ranges of the field bus module
Configurable I/O address range
Depending on the protocol variant and the operating mode,
field bus module SPC200−COM−DN2 provides the following
I/O address ranges:
Protocol
variant
Operating
mode
I/O address
range
*)
I/O byte
Functions
DeviceNet IO
Start/Stop
I10.0 ... I10.15
2 bytes
Control signals and freely
programmable inputs
I11.0 ... I13.15
0, 2, 4, 6
bytes
Freely programmable inputs (optional)
Q10.0 ... Q10.15
2 bytes
Control signals and freely
programmable outputs
Q11.0 ... Q13.15
0...6 bytes
Freely programmable outputs (optional)
Record Select
I10.0 ... I10.15
2 bytes
Control signals
I11.0 ... I11.9
2 bytes
Record number
Q10.0 ... Q10.15
2 bytes
Control signals
DeviceNet
profiles
(always)
I10.0 ... I13.15
8 bytes
For exact assignment see section 5.2.
profiles
Q10.0 ... I13.15
8 bytes
*)
I/O address range of the field bus module; address specifications as viewed by the SPC200
Read example: You are using the field bus module in the
protocol variant DeviceNet IO and the SPC200 in Start/Stop
mode. Besides the control signals in I/Q 10 (2 bytes each),
you wish to use a further two bytes of freely programmable
inputs/outputs. You then assign IĂ10.0 ... IĂ11.15 (= 4 bytes)
and QĂ10.0 ... QĂ11.15 (= 4 bytes).
An overview of all address ranges of the SPC200 (IĂ0...13,
QĂ0...13) can be found in section 1.5.