Chapter 7 Troubleshooting
Code Message
Description and Solution
E3040 Operation failed because Project is deleted.
The project may already have been deleted. Update the information on
the Project List Page, and check that the project exists.
E3041 Serial no is invalid. Activation failed.
Check the license number, and enter it correctly.
E3042 Server has not been activated. Adding option to
software failed.
Register the server license first, and then add options.
E3043 Tag upgrade option's serial no is invalid. Fail to add
option's serial no.
Adding the option would cause the number of tags to exceed the
maximum recording tags in the project. In the server information dialog
box, check the current number of tags, and check whether the option
that you tried to add is appropriate.
E3044 Part of the data files can not be deleted.
Some of the data files that you tried to delete could not be deleted.
They may be in use.
E3045 Part of the data files can not be opened.
Some of the data files that you tried to open could not be opened.
Update the information on the Data files Page, and check that the data
files exist.
E3046 Failed in registration.The administrator authority is
required.Please restart as an administractor or run as
administrator and restart.
Log on again as a Windows administrator. Or, choose Run as
administrator when starting Data Logging Software. (In Windows 7,
right-click the software icon, and click Run as administrator.)
E3047 Insufficient memory available to the OS. Operation
failed.
Try the following:
• Stop other running programs.
• Reduce the number of simultaneously running projects.
• Increase the PC RAM.
• If you are using a 32 bit edition, try a 64 bit edition.
E3048 Since the number of tags in the imported project
configuration information exceeded the number of tags
supported by the current server,failed to import.
The number of tags in the project that you are trying to import exceeds
the number of tags handled by the current server. Consider increasing
the number of tags handled by the server.
E3049 Failed to operate some projects or all project at once. If Start Monitoring Simultaneously cannot be executed, it could be any
of the following reasons.
• The number of simultaneously running projects or simultaneously
connected devices exceeds the limit.
• There is not enough available memory on Windows.
If Start Recording Simultaneously cannot be executed, it could be any
of the following reasons in addition to the reasons listed above.
• The data save destination folder failed to be created.
Close projects that do not require data collection. To start recording,
change the data file save destination folder.
E3050 Insufficient memory available to the OS. Project will
close.
Try the following:
• Stop other running programs.
• Reduce the number of simultaneously running projects.
• Increase the PC RAM.
• If you are using a 32 bit edition, try a 64 bit edition.
E3051 Fail to start monitoring because the necessary setting
is not correct.
There is an error in the information that is used during data collection.
Check for errors in Modbus device definition files.
E3052 Operation failed because device has been deleted.
Update the device information on the Registered Devices List.
E3053 Searching is not allowed because auto-search in
progress.
Another client is searching devices with different search conditions.
Wait for the search operation to complete, and try searching again.